Research, assessment and proposals on resolving power quality problem for the power supply system of Lam Dong alumina refinery, Vietnam

https://doi.org/10.17073/2500-0632-2021-2-121-127

Abstract

Alumina production is rather complex technological process of processing mineral raw materials that requires development of effective technological solutions, including in terms of efficiency of using electric energy. The paper is devoted to studying the power supply system of an alumina refinery inLam Dong Province,Vietnam. The tasks that need to be solved for improving the power quality in the power supply system were analyzed. It was shown that non-linear loads significantly degrade the power quality that in turn leads to equipment damage, malfunction and decreasing the refinery productivity. Models of the refinery power supply system were developed and, using which, the quality of power was assessed at the 6 kV voltage utility bus of the power supply system, as well as at the 6 kV and 0.4 kV buses of distribution substations of individual refinery’s subdivisions. Analysis of the simulation findings showed that the nonlinear loads lead to significant distortions of sinusoidal forms of voltages and currents, and decreasing the power factor. Based on the simulation results, it was concluded that voltage harmonics and current harmonics at nonlinear load at the low voltage buses of 0.4 kV and at the buses of 6 kV exceed the permissible limits of the harmonics in accordance with IEEEST519-1992 international standard. Proposals were developed for improving the power quality in the refinery power supply system. For suppressing higher harmonics of current and voltage, it was recommended to use special power quality regulators in the alumina refinery power supply system. It was proposed to use active harmonic filters as the power quality regulators. The proposed solutions allowed obtaining practically sinusoidal forms of voltages and currents in the alumina refinery power supply system.

About the Author

Thanh Lich Do
Dalat Vocational College
Viet Nam

Thanh Lich Do – Lecturer at the Department of Electrical Systems

Da Lat



References

1. Zhezhelenko I. V., Shidlovskiy A. K., Pivnyak G. G. et al. Electromagnetic compatibility of consumers. Мoscow: Mashinostroenie Publ.; 2012. 351 p. (In Russ.). URL: https://core.ac.uk/download/pdf/48402076.pdf (Accessed: 03.01.2021).

2. Zhelezko Yu. S. Electric power losses. Reactive power. Power quality. Мoscow: ENAS Publ. House; 2009. 456 p. (In Russ.).

3. Kartashev I. I., Tul’skiy V. I., Shamonov R. G. et al. Electric energy quality management. Мoscow: MEI Publ.; 2006. 320 p. (In Russ.).

4. Karandaev A. S., Kornilov G. P., Khramshin T. R. et al. Analysis of power quality indicators in an industrial power supply system with high-power thyristor drives. Vestnik of Nosov Magnitogorsk State Technical University. 2006;(3):6–11. (In Russ.). URL: http://vestnik.magtu.ru/content/%D0%92%D0%B5%D1%81%D1%82%D0%BD%D0%B8%D0%BA%20%D0%9C%D0%93%D0%A2%D0%A3%20%D0%B7%D0%B0%202006%20%D0%B3%D0%BE%D0%B4,%20%D0%9D%D0%BE%D0%BC%D0%B5%D1%80%203.pdf

5. German-Galkin S. G. Virtual laboratories for semiconductor systems in the Matlab-Simulink environment. St. Petersburg: Lan’ Publ.; 2013. 488 p. (In Russ.).

6. Abramov B. I., Parfenov B. M., Shevyrev Yu. V. Choice methods of the parameters of filter compensating stepped type devices for thyristor electric drives. Russian Electrical Engineering. 2001;(1):38–42.

7. Dobrusin L. A. Compensation filter devices for converter equipment. Мoscow: NTF Energoprogress Publ.; 2003. 84 p. (In Russ.).

8. Shevyreva N. Yu. The influence of multistage filter compensation device on energy guality during the operation of drill rigs with variable-frequency electric drive. Mining informational and analytical bulletin. 2015;(1):408–415. (In Russ.). URL: https://www.elibrary.ru/item.asp?id=23005905

9. Shevyrev Yu. V. Improving electric power quality in networks with semiconductor converters. Mining informational and analytical bulletin. 2011;(4):234–241. (In Russ.). URL: https://www.elibrary.ru/item.asp?id=17265227

10. Kanaan H. Y., Hayek A., Al-Haddad K., Rahmani S. Carrier-based linear decoupling control of a three-phase four-leg shunt active power filter. In: IECON 2007 – 33rd Annual Conference of the IEEE Industrial Electronics Society. 2007, pp. 1839–1844. https://doi.org/10.1109/IECON.2007.4459970

11. Sychev Yu. A. Analysis of hybrid system effectiveness for correcting power quality indicators in power supply systems of mining and processing industry enterprises. In: Innovations and prospects for the development of mining machinery and electrical machinery manufacturing: IPDME-2017. 2017, pp. 223–226. (In Russ.).

12. Egorov A. N., Semenov A. S., Kharitonov Ya. S., Fedorov O. V. Efficiency of variable frequency drive in diamond mining. Gornyi Zhurnal. 2019;(2):77–82. (In Russ.). https://doi.org/10.17580/gzh.2019.02.16

13. Ojo A., Awodele K., Sebitosi A. Load compensation in a three-phase four wire distribution system considering unbalance, neutral current elimination and power factor improvement. In: 2019 Southern African Universities Power Engineering Conference/Robotics and Mechatronics/Pattern Recognition Association of South Africa (SAUPEC/RobMech/PRASA). 2019, pp. 389–394. https://doi.org/10.1109/RoboMech.2019.8704821

14. Sarvarov A. S., Shevyrev Yu. V., Fedorov O. V. Assessment of cost-effectiveness of improving energy performance in networks with semiconductor converters. Bulletin of the South Ural State University. Series “Power Engineering”. 2015;15(3):11–19. (In Russ.). https://doi.org/10.14529/power150302


Review

For citations:


Do T.L. Research, assessment and proposals on resolving power quality problem for the power supply system of Lam Dong alumina refinery, Vietnam. Mining Science and Technology (Russia). 2021;6(2):121-127. (In Russ.) https://doi.org/10.17073/2500-0632-2021-2-121-127